Aspen Mechanical Peristaltic Alarm Signal Air Conditioning Pump FP2079 The Mechanical peristaltic pump operates with a high level alarm output. The pump is designed to be mounted remotely if required and has a 3 metre (9.8ft) lead to the float switch. Alarm option Self-priming lifts 3 metres 12 metres discharge head Water flow rate: 6.25 ltrs per hr @ 12 metres head No siphoning back No loud sound from dry running Manual test switch Pumps water, contaminated water & air Pump rating: 0.2A, 230V AC Alternative voltages available Fire retardant plastics Inlet/outlet size: 6mm Push-in plug Wall-mounted bracket Dimensions: 145mm(H) x 160mm(W) x 83mm(D) The Aspen Mechanical peristaltic pump is the latest model. The pump is designed to be mounted remotely if required and has a 3 metre (9.8ft) lead to the float switch. Simply connect the float switch to the condensate tray or drainpipe fitting. Peristaltic pumps have the advantage of pumping dirty water or pumping dry without damaging the pump or making a noise.
Aspen Mechanical Pump Service Guide. Inspect pump head regularly and change the pump head tube every 12 months or more frequently if required. If any problems with the pump occur check the tube first! To remove pump head make sure the roller assembly is vertical. Remove transparent cover and fit replacement pipe. The addition of a smear of silicon grease will ease the refitting of the lid, reducing potential friction noise. This only takes 3 minutes! The test switch should always be returned to the NORMAL position after inspection. ELECTRICAL CONNECTIONS: Brown - Live Blue - Neutral Green/Yellow - Earth Technical Specifications. Self priming lifts 3 metres (9.8ft) 12 metres (40ft) discharge head Water flow rate: 6.25 ltrs (1.65 US gallons) per hr @ 12 metres (40ft) No siphoning back No loud sound from dry running Pumps water, fibrously contaminated water and air Fits into ceiling void Pump rating: 0.2A, 230V AC Alternative voltages available Maximum water temperature: 40??C Fire retardant plastics Available with an alarm option
Installation Notes Install this pump inside the unit or above a false ceiling. Connect live, neutral and earth to the evaporator. The mechanical pump now has a new push in plug which makes installation and maintenance easier. Product Specification Sheet
|