EcoWarrior Refrigerant Recovery Unit.
• Liquid recovery rate: up to 80kgs/hr
• Vapour recovery rate: up to 30kgs/hr
• Push/pull: up to 320kgs/hr
• 230V & 110V models available
• 500W oil-less compressor
• High Pressure cut out of 410PSIG
• Large condenser and high air flow
• Suitable for most types of refrigerant,
both liquid and vapour (see Page 4)
• Purge facility
• Rugged, moulded case
IMPORTANT NOTE:
THIS EQUIPMENT MUST ONLY BE USED BY TRAINED AND COMPETENT ENGINEERS.
DIMENSIONS
Height Depth Width Weight
358mm 275mm 395mm 12.5kg
MOTOR WARNING:
The crankcase cover plate is designed
for 340psig maximum pressure. Pressure
above this will cause excessive deflection
and leakage.
COOLING REQUIREMENTS
HEAD AND CYLINDER:
The multi-refrigerant compatible
seals cannot exceed 250°F without
degradation. Cooling air must be directed
through head and cylinder fins to prevent
premature seal failures.
MOTOR:
Cooling air must be provided through the
motor to maintain UL temperature rise
limits of 95°C.
Model Motor Rectifier (Diotec)
500CAR75 110-115V 50/60Hz DB2506P/T
500CDR75 200-240V 50/60Hz DB2506P/T
• Maximum exhaust pressure: 435 psig
• Compression Ratio Min.: 50 (11”Hg@
435psi (exhaust) and 29.5” Hg
barometer)
• Maximum Vacuum @ open exhaust:
28.5” Hg
• Refrigerants: R-11, R-12, R-22,
R-113, R-114, R-123, R-134A,
R-404, R-407C, R-410A, R-500, R-502.
• Average service free life: 1000hrs*
|