Armafinish Armaflex Paint - Technical Product Data  |  |  | | Armafinish FR is a water-based coating using an advanced terpolymer resin system. The properly applied coating is particularly suitable for the protection of Armaflex flexible thermal insulation materials against sunlight, U.V. radiation and chemical attack. The coating, when fully cured, maintains the flexibility, resistance to water vapour and fire performance of the Armaflex material. Where resistance to damage is a particular requirement the coating may be further strengthened using a random mesh glass fibre scrim. |  | |
| Surface preparation | The Armaflex surface should be clean, dry and free from any oil, grease, organic growth and other extraneous substances that may affect adhesion and cure. Surfaces may be cleaned using Armaflex cleaner, which should be allowed to evaporate completely before the application of the coating. | | Application conditions | The coating may be applied if the ambient temperature is not likely to fall below 5 ??C, and the relative humidity is below 90%, providing that the dew point is not exceeded. | Coverage
| | Coat | litres per m?? | m?? per litre | wet film (microns) | dry film (microns) | | 1st | 0.275 | 3.6 | 275 | 130 | | 2nd | 0.275 | 3.6 | 275 | 130 | | Overall | 0.55 | 1.8 | 550 | 260 | Where practical the first coat should be in a contrasting colour to the second coat so that adequate coverage is obtained by obliterating the substrate. To build up the required thickness Armafinish FR should not be brushed out, as with conventional paints, but rather dabbed on to the surface and lightly smoothed out. When using brush application the second coat should be applied at right angles to the first, if it is practical to do so. | | Drying time | Under normal conditions the Armafinish FR should be dry within 1 - 2 hours. Low temperature and / or high humidity will progressively increase the time for the coating to dry but will not affect the ultimate cure. The second coat may be applied as soon as the first coat is thoroughly dry and within 3 days of the first coat application. | | Service temperature | -50 ??C to + 60 ??C. | | Fire performance | When applied at the recommended thickness to Class O Armaflex and tested to BS 476 Parts 6 and 7 the system complies with the requirements of paragraph A12(b) of Approved Document B ÈÃ Fire SafetyÈÃÍ of the Building Regulations 1991 to give the Class O classification. (See WFRC Certificates WARRES 60737 and 60738. Copies of full test certificates are available on request from Armacell Customer Services Department). | | Solids content | 48% by volume Specific gravity: 1.39 | | Storage | Store in frost-free conditions in tightly sealed container. Keep away from sources of heat. | | Shelf life | 2 years in unopened containers, when stored as directed above. | | Reinforcement | To reinforce the surface use Arma-Chek T Web random mesh glass fibre which is embedded into the first layer of coating while it is still wet. Both coats should be applied at double the thickness recommended above (i.e. overall coverage rate of less than 1 square metre per litre). The second layer should be applied so that the Arma-Chek Web is virtually obliterated. Please note that the drying time will be extended.
Armafinish FR paint is only suitable for reinforcement over small areas. Where it is required to reinforce large areas it is preferable to use one of the ?? Arma-Chek covering systems. | | Colours | Standard - white and light grey (RAL7035). Special colours may be available to order, dependent upon the exact colour and quantity required. Batch quantities will be supplied. | | Pack size | 2.5 litres, in plastic pails with handle | | Application equipment | May be applied by brush, short pile roller or airless spray (at 2500-3000 psi with 19-20 thou tip size). | | Cleaning | All brushes and equipment should be cleaned with water immediatelyafter use. |
|